Code for Size of Cable for Motor

0 13
Avatar for spyro
Written by
3 years ago

Size of cable for Branch circuit which has Single Motor connection is 125% of Motor Full Load Current Capacity.

Example:

What is the minimum rating in amperes for Cables supplying 1 No of 5 hp, 415 V, 3-phase motor at 0.8 Power factor.

Full load current for 5 hp = 7Amp.

Min capacity of cable = (7x125%) = 8.75 Amp.

Size of cable for Group of Motor or Electrical Loads

Cables or Feeder which is supplying more than one motors other load(s), shall have an ampacity not less than 125 % of the full-load current rating of the highest rated motor plus the sum of the full-load current ratings of all the other motors in the group, as determined by 430.6(A).

For Calculating minimum Ampere Capacity of Main feeder and Cable is 125% of Highest Full Load Current + Sum of Full Load Current of remaining Motors.

Example What is the minimum rating in amperes for Cables supplying 1 No of 5 hp, 415-volt, 3-phase motor at 0.8 Power Factor , 1 No of 10 hp, 415-volt, 3-phase motor at 0.8 Power Factor, 1 No of 15 hp, 415-volt, 3-phase motor at 0.8 Power Factor and 1 No of 5hp, 230-volt, single-phase motor at 0.8 Power Factor?

• Full-load currents for 5 hp = 7A

• Full-load currents for 10 hp = 13A

• Full-load currents for 15 hp = 19A

• Full-load currents for 10 hp (1 Ph) = 21A

• Here Capacity wise Large Motor is 15 Hp but Highest Full Load current is 21Amp of 5hp Single Phase Motor so 125% of Highest Full Load current is 21X125%=26.25A

• Min Capacity of Cable= (26.25+7+13+19) =65.25 A

Size of Overload Protection

Overload protection (Heater or Thermal cut out protection) would be a device that thermally protects a given motor from damage due to heat when loaded too heavy with work.

All continuous duty motors rated more than 1HP must have some type of an approved overload device.

An overload shall be installed on each conductor that controls the running of the motor rated more than one horsepower. NEC 430/37 plus the grounded leg of a three phase grounded system must contain an overload also. This Grounded leg of a three phase system is the only time you may install an overload or over – current device on a grounded conductor that is supplying a motor.

To Find the motor running overload protection size that is required, you must multiply the F.L.C. (full load current) with the minimum or the maximum percentage ratings as follows;

Maximum Overload

• Maximum overload = F.L.C. (full load current of a motor) X allowable % of the maximum setting of an overload,

• 130% for motors, found in NEC Article 430/34. • Increase of 5% allowed if the marked temperature rise is not over 40 degrees or the marked service factor is not less than 1.15. Minimum Overload

• Minimum Overload = F.L.C. (full load current of a motor) X allowable % of the minimum setting of an overload, • 115% for motors found in NEC Article 430/32/B/1. • Increase of 10% allowed to 125% if the marked temperature rise is not over 40 degrees or the marked service factor is not less than 1.15.